The Smith Meter Model 200-50B is a hydraulically operated, diaphragm-actuated, globe-pattern automatic pressure reducing control valve that holds a steady downstream pressure regardless of upstream fluctuations. A normally-open 50B pilot in the downstream side of the pilot loop senses outlet pressure through an integral sense line; as downstream pressure approaches the setting the pilot restricts the cover vent path and the main valve throttles. It is a modulating valve for most non-dead-end systems where downstream equipment needs protection from excessive pump pressure. Control range is limited to flow rates above 2% of nominal maximum flow.
Key specifications
- Sizes / nominal flow: 2" 130 USGPM (492 L/min), Cv 50; 3" 420 USGPM (1,600 L/min), Cv 133; 4" 600 USGPM (2,250 L/min), Cv 204; 6" 1,000 USGPM (3,750 L/min), Cv 436
- Pressure rating: Class 150 ANSI, 285 psi (19.6 bar); Class 300 ANSI, 300 psi (20.7 bar); derate per ASME B16.5
- Maximum viscosity: 200 SSU (40 mPa·s); above that consult factory
- Seals / temperature: Buna-N valve diaphragm with Viton pilot: 0 to 160 °F; Viton throughout: 10 to 350 °F
- Materials: Carbon steel Model 200 body (stainless, carbon steel, ductile iron internals); 09SC strainer, Model 13 needle valve and 50B pilot in carbon steel
- Weight: 2" 48 lb (22 kg); 3" 85 lb (39 kg); 4" 138 lb (63 kg); 6" 260 lb (118 kg)
- Add-on functions: Solenoid block (30A), rapid shutdown (30B), maximum rate of flow (40A), back pressure (60A), check and thermal relief (80B/07)
Ordering information
The bulletin has no position-by-position model code. Per its ordering section, specify:
- Valve size (2", 3", 4" or 6") and flange class
- Liquid name and specific gravity or API gravity
- Temperature range and viscosity range (minimum, normal, maximum)
- Maximum working pressure and the pressure setting(s) required
- Seals: Buna-N or Viton; any additional pilot functions
Bulletin notes: the bulletin title reads "Pressure-Limiting Valve" while the text describes a pressure reducing valve; the pressure-drop formula beside the flow table is garbled in the PDF (it is the usual Cv relation using specific gravity and flow); The dimension table prints the 2" pilot-envelope dimension D as 7.5 in (140 mm); 7.5 in is about 191 mm. For a lower-pressure-drop reducing valve see the 200-64A.
Pricing and lead time are quoted per configuration. Send the model code (or the details above) with your product and operating conditions to Flow Measurement Services for a quote. Specifications summarized from Smith Meter bulletin SS03015 Rev 0.4 (8/17); confirm current data with the factory before ordering.
Smith Meter (formerly FMC Technologies / TechnipFMC Measurement Solutions), now manufactured by Guidant. Flow Measurement Services supplies and services Smith Meter equipment.